Description
Vertiv LIEBERT GXT5 ON-LINE 5000VA 230V LCD PF1.0 5U EXTENDED RUN RACK/TOWER RAIL KIT AND WEBCARD BUNDLED GXT5-5000IRT5UXLN (3 Years Manufacture Local Warranty In Singapore)
Features
- Intelligent and Efficient UPS protection for your mission-critical applications
- Unity Power Factor (PF=1.0) means more active power available so more loads
- Higher efficiency through optimized energy management and lower heat dissipation, providing energy and cost savings
- Powerful charging capability for minimum battery recharging time
- Programmable sockets help to extend runtime for the most critical loads and smart disconnection of the less critical ones
Technical Information
Model Number GXT5-5000IRT5UXLN
Ratings (VA/W) 5000 VA / 5000 W
Dimensions and Weight
Dimensions (mm) Unit, W×D×H 430×630×217
Unit Weight (kg) 74.5
Input AC Parameters
Operating Frequency, 60 Hz (Factory default is 50 Hz )
Factory Default Voltage 230 VAC
Operating Voltage Range Without Battery Operation 176 to 288 VAC (100 to 176 VAC with power derating)
176 to 288 VAC (100 to 176 VAC with power derating) 288 VAC
Input Frequency Without Battery Operation 40 to 70 Hz
Output AC Parameters
AC-AC Efficiency 94%
Factory Default Voltage 230 VAC
Factory Default Voltage 50 Hz or 60 Hz, Nominal
Waveform Pure Sinewave
Output Power Connection – Output Terminal Block
Main Mode Overload >150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous
Internal Battery
Charger Current :2.25 A (default), maximum 5 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating – 2×8 x12V x 90 AH
Back-up Time at Full Load 7
Back-up Time at Half Load 19
Bypass Protection Limits
Upper-limit Selections + 10%, + 15%, + 20%; default + 10%.
Lower – limit Selections – 10% – 15% -20% default – 15%
Disable-bypass Operation When the input frequency prevents synchronous operation
General
Operating Temperature, °C Full power up to 40 oC (up to 50 oC with derating)
Storage Temperature, °C – 15 to + 40
Relative Humidity – 0 – 95% non-considering
Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
Audible Noise – <55 dBA
Safety UL-1788 (Fifth Edition),C-UL listed, IEC 62040-1: 2017 Edition 2.0, EN 62040-1:2008+A1:2013
EMI/EMC/C-Tick EMC = IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A) CISPR22 Class A (RFI)
ESD IEC/EN EN61000-4-2, Level 4, Criteria B
Radiated Susceptibility – IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient- IEC/EN EN61000-4-4, Level 4, Criteria B
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
Transportation ISTA Procedure 1E
Also seen in the collections
Related Products
Full Collection for Vertiv
Vertiv Liebert GXT5 UPS
Payment & Security
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.