Vertiv LIEBERT GXT5 ON-LINE 5000VA 230V LCD PF1.0 5U EXTENDED RUN RACK/TOWER RAIL KIT AND WEBCARD BUNDLED GXT5-5000IRT5UXLN (3 Years Manufacture Local Warranty In Singapore)

VertivSKU: GXT5-5000IRT5UXLN
No reviews

Price:
Sale price$ 4,507.00 SGD

Description

Vertiv LIEBERT GXT5 ON-LINE 5000VA 230V LCD PF1.0 5U EXTENDED RUN RACK/TOWER RAIL KIT AND WEBCARD BUNDLED  GXT5-5000IRT5UXLN (3 Years Manufacture Local Warranty In Singapore)

Features

  • Intelligent and Efficient UPS protection for your mission-critical applications
  • Unity Power Factor (PF=1.0) means more active power available so more loads
  • Higher efficiency through optimized energy management and lower heat dissipation, providing energy and cost savings
  • Powerful charging capability for minimum battery recharging time
  • Programmable sockets help to extend runtime for the most critical loads and smart disconnection of the less critical ones

Technical Information

Model Number  GXT5-5000IRT5UXLN

Ratings (VA/W)  5000 VA / 5000 W

Dimensions and Weight

Dimensions (mm) Unit, W×D×H  430×630×217

Unit Weight (kg) 74.5

Input AC Parameters 

Operating Frequency, 60 Hz (Factory default is 50 Hz )

Factory Default Voltage 230 VAC

Operating Voltage Range Without Battery Operation 176 to 288 VAC (100 to 176 VAC with power derating)

176 to 288 VAC (100 to 176 VAC with power derating) 288 VAC

Input Frequency Without Battery Operation 40 to 70 Hz

Output AC Parameters 

AC-AC Efficiency 94%

Factory Default Voltage 230 VAC

Factory Default Voltage 50 Hz or 60 Hz, Nominal

Waveform Pure Sinewave

Output Power Connection – Output Terminal Block

Main Mode Overload >150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous

Internal Battery

Charger Current :2.25 A (default), maximum 5 A

Type Valve-regulated, non-spillable, lead acid

Qty x V x Rating  – 2×8 x12V x 90 AH

Back-up Time at Full Load  7

Back-up Time at Half Load  19

Bypass Protection Limits

Upper-limit Selections + 10%, + 15%, + 20%; default + 10%.

Lower – limit Selections – 10% – 15% -20% default – 15%

Disable-bypass Operation When the input frequency prevents synchronous operation

General

Operating Temperature, °C Full power up to 40 oC (up to 50 oC with derating)

Storage Temperature, °C – 15 to + 40

Relative Humidity – 0 – 95% non-considering 

Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating

Audible Noise – <55 dBA

Safety UL-1788 (Fifth Edition),C-UL listed, IEC 62040-1: 2017 Edition 2.0, EN 62040-1:2008+A1:2013

EMI/EMC/C-Tick EMC =  IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A) CISPR22 Class A (RFI)

ESD IEC/EN EN61000-4-2, Level 4, Criteria B

Radiated Susceptibility – IEC/EN EN61000-4-3, Level 3, Criteria A

Electrical Fast Transient- IEC/EN EN61000-4-4, Level 4, Criteria B

Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B

Transportation ISTA Procedure 1E

Also seen in the collections