Description
Vertiv LIEBERT GXT5 ON-LINE 6000VA 230V LCD PF1.0 5U EXTENDED RUN RACK/TOWER RAIL KIT AND WEBCARD BUNDLED GXT5-6000IRT5UXLN (3 Years Manufacture Local Warranty In Singapore)
Description
The Liebert® GXT5™ UPS is a single phase, online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system. The new Liebert® GXT5™ from Vertiv™ is an advanced version of the widely-regarded GXT UPS Series. GXT5 is ideally suited to protect critical infrastructure in both centralized and edge network applications.
- Banking, Financial and Insurance
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Manufacturing
- Retail and Wholesale
- Telecom
- Transportation
Warranty: 3 Years Warranty
Technical Information
Ratings (VA/W) 6000 VA / 6000 W
Dimensions and Weight
Dimensions (mm) Unit, W×D×H 430×630×217
Unit Weight (kg) 70.8
Input AC Parameters
Operating Frequency, Nom 50 or 60 Hz (Factory default is 50 Hz )
Factory Default Voltage 230 VAC
Operating Voltage Range Without Battery Operation 176 to 288 VAC (100 to 176 VAC with power derating)
176 to 288 VAC (100 to 176 VAC with power derating) 288 VAC
Input Frequency Without Battery Operation 40 to 70 Hz
Output AC Parameters
AC-AC Efficiency 94%
User-configurable Voltage 200/208/220/230/240 VAC
Factory Default Voltage 230 VAC
Factory Default Voltage 50 Hz or 60 Hz, Nominal
Waveform Pure Sinewave
Output Power Connection – Output Terminal Block
Main Mode Overload >150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous
Internal Battery
Charger Current :2.25 A (default), maximum 5 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating – 2×8 x12V x 90 AH
Back-up Time at Full Load 5,5
Back-up Time at Half Load 14,5
Bypass Protection Limits
Upper-limit Selections + 10%, + 15%, + 20%; default + 10%.
Lower – limit Selections – 10% – 15% -20% default – 15%
Disable-bypass Operation When the input frequency prevents synchronous operation
General
Operating Temperature, °C Full power up to 40 oC (up to 50 oC with derating)
Storage Temperature, °C – 15 to + 40
Relative Humidity – 0 – 95% non-considering
Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
Audible Noise – <55 dBA
Safety UL-1788 (Fifth Edition),C-UL listed, IEC 62040-1: 2017 Edition 2.0, EN 62040-1:2008+A1:2013
EMI/EMC/C-Tick EMC = IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A) CISPR22 Class A (RFI)
ESD IEC/EN EN61000-4-2, Level 4, Criteria B
Radiated Susceptibility – IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient- IEC/EN EN61000-4-4, Level 4, Criteria B
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
Transportation ISTA Procedure 1E